View CSAF Summary Hitachi Energy is aware of the vulnerability, CVE-2022-4304 in the OSS component OpenSSL, that affects the GMS600 versions that are listed below. An attacker successfully exploiting this vulnerability could send trial messages to the server and record the time taken to process them. After a sufficiently large number of messages the attacker could recover the pre-master secret used for the original connection and thus be able to decrypt the application data sent over that connec
View CSAF Summary ABB became aware of vulnerability in the product versions listed as affected in the advisory. An update is available that replaces an outdated third-party component. Although no successful exploitation was observed during testing of the affected B&R products, the identified vulnerabilities could present potential attack vectors that might enable unauthorized access, data exposure, or remote code execution. The following versions of ABB B&R Automation Studio are affected
View CSAF Summary An update is available that resolves a vulnerability identified by B&Rs internal security analysis in the product versions listed as affected in this advisory. An attacker who successfully exploited these vulnerabilities could take over a remote session or execute code in the context of the user’s browser session. The following versions of ABB B&R Automation Runtime are affected: Automation Runtime <6.4, 6.4 (CVE-2025-3449, CVE-2025-3448, CVE-2025-11498) CVSS V
View CSAF Summary ABB became aware of vulnerability in the product versions listed as affected in the advisory. An update is now available that addresses and remediates the vulnerability. A network attacker could exploit the vulnerabilities to execute remote code, initiate DoS attacks, conduct DNS cache poisoning, or extract sensitive information. The following versions of ABB B&R PCs are affected: APC4100 <1.09, 1.09 (CVE-2023-45229, CVE-2023-45230, CVE-2023-45231, CVE-2023-45232, CVE-2
CISA has added two new vulnerabilities to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2025-34291 Langflow Origin Validation Error Vulnerability CVE-2026-34926 Trend Micro Apex One (On-Premise) Directory Traversal Vulnerability These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Kn
CISA has added seven new vulnerabilities to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2008-4250 Microsoft Windows Buffer Overflow Vulnerability CVE-2009-1537 Microsoft DirectX NULL Byte Overwrite Vulnerability CVE-2009-3459 Adobe Acrobat and Reader Heap-Based Buffer Overflow Vulnerability CVE-2010-0249 Microsoft Internet Explorer Use-After-Free Vulnerability CVE-2010-0806 Microsoft Internet Explorer Use-After-Free Vulnerability CVE-2026-410
View CSAF Summary Schneider Electric is aware of a vulnerability in its EcostruxureTM Machine Expert HVAC product. The [EcostruxureTM Machine Expert HVAC](https://www.se.com/ww/en/download/document/EcoStruxureME_HVAC/) product is a programming software for Modicon M171-M172 logic controllers. Failure to apply the remediation provided below may risk in revealing sensitive information, which could result in disclosing protected source code, leading to loss of confidentiality. The following version
View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to take control of the victim's browser. The following versions of Kieback & Peter DDC Building Controllers are affected: DDC4002 <=1.12.14 (CVE-2026-4293) DDC4100 <=1.12.14 (CVE-2026-4293) DDC4200 <=1.12.14 (CVE-2026-4293) DDC4200-L <=1.12.14 (CVE-2026-4293) DDC4400 <=1.12.14 (CVE-2026-4293) DDC4002e <=1.23.4 (CVE-2026-4293) DDC4200e <=1.23.4 (CVE-2026-4293) DDC4400e <=1.23.4 (CV
View CSAF Summary A buffer overflow vulnerability in the User-ID™ Authentication Portal (aka Captive Portal) service of Palo Alto Networks PAN-OS software allows an unauthenticated attacker to execute arbitrary code with root privileges on the PA-Series and VM-Series firewalls by sending specially crafted packets. Siemens is preparing fix versions and recommends countermeasures for products where fixes are not, or not yet available. Customers are advised to consult and implement the workarounds
View CSAF Summary An update is available that resolves vulnerability in the product versions listed as affected in this advisory. A path traversal vulnerability in these products can allow unauthenticated users to gain access to restricted directories. Exploiting this vulnerability can lead to complete system compromise and exposure of sensitive information. The following versions of ABB CoreSense HM and CoreSense M10 are affected: CoreSense™ HM <=2.3.1, 2.3.4 (CVE-2025-3465) CoreSense™ M10
View CSAF Summary Successful exploitation of these vulnerabilities could allow an attacker to perform unauthenticated remote code execution. The following versions of ScadaBR are affected: ScadaBR 1.2.0 (CVE-2026-8602, CVE-2026-8603, CVE-2026-8604, CVE-2026-8605) CVSS Vendor Equipment Vulnerabilities v3 9.1 ScadaBR ScadaBR Missing Authentication for Critical Function, Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection'), Cross-Site Request Forgery
View CSAF Summary Successful exploitation of this vulnerability could result in information disclosure, including capture of camera account credentials. The following versions of ZKTeco CCTV Cameras are affected: SSC335-GC2063-Face-0b77 Solution CVSS Vendor Equipment Vulnerabilities v3 9.1 ZKTeco ZKTeco CCTV Cameras Authentication Bypass Using an Alternate Path or Channel Background Critical Infrastructure Sectors: Commercial Facilities Countries/Areas Deployed: Worldwide Company
CISA has added one new vulnerability to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation. CVE-2026-42897 Microsoft Exchange Server Cross-Site Scripting Vulnerability This type of vulnerability is a frequent attack vector for malicious cyber actors and poses significant risks to the federal enterprise. Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the KEV Catalog as a living list
View CSAF Summary ROS# contains a ROS service file_server, that before version 2.2.2 contains a path traversal vulnerability which could allow an attacker to access, i.e. read and write, arbitrary files, which are accessible with the user rights of the user that runs the service, on the system that hosts service. Siemens has released a new version for ROS# and recommends to update to the latest version. The following versions of Siemens Siemens ROS# are affected: ROS# vers:intdot/<2.2.2
View CSAF Summary Siemens gPROMS Web Applications Publisher (gWAP) is affected by a remote code execution vulnerability introduced through a third-party component, namely the Axios HTTP client library. The vulnerability stems from a specific "Gadget" attack chain that allows prototype pollution in other third-party libraries, potentially allowing an attacker to execute arbitrary code. Siemens has released a new version for gWAP and recommends to update to the latest version. The following versio
View CSAF Summary SIMATIC CN 4100 contains multiple vulnerabilities which could potentially lead to a compromise in availability, integrity and confidentiality. Siemens has released a new version for SIMATIC CN 4100 and recommends to update to the latest version. The following versions of Siemens SIMATIC are affected: SIMATIC CN 4100 vers:intdot/<5.0 CVSS Vendor Equipment Vulnerabilities v3 9.6 Siemens Siemens SIMATIC NULL Pointer Dereference, Reachable Assertion, Use After Fr
View CSAF Summary Ruggedcom Rox contains an input validation vulnerability in the Scheduler functionality that could allow an authenticated remote attacker to execute arbitrary commands with root privileges on the underlying operating system. Siemens has released new versions for the affected products and recommends to update to the latest versions. The following versions of Siemens Ruggedcom Rox are affected: RUGGEDCOM ROX MX5000 vers:intdot/<2.17.1 RUGGEDCOM ROX MX5000RE vers:intdot/
View CSAF Summary Ruggedcom Rox before v2.17.1 contain multiple third-party vulnerabilities. Siemens has released new versions for the affected products and recommends to update to the latest versions. The following versions of Siemens Ruggedcom Rox are affected: RUGGEDCOM ROX MX5000 vers:intdot/<2.17.1 (CVE-2019-13103, CVE-2019-13104, CVE-2019-13106, CVE-2019-14192, CVE-2019-14193, CVE-2019-14194, CVE-2019-14195, CVE-2019-14196, CVE-2019-14197, CVE-2019-14198, CVE-2019-14199, CVE-2019-14200
View CSAF Summary Simcenter Femap is affected by heap based buffer overflow vulnerability in Datakit library that could be triggered when the application reads files in IPT format. If a user is tricked to open a malicious file with the affected application, an attacker could leverage the vulnerability to perform remote code execution in the context of the current process. Siemens has released a new version for Simcenter Femap and recommends to update to the latest version. The following versions
View CSAF Summary Successful exploitation of these vulnerabilities could allow an attacker to bypass authentication and execute code. The following versions of Universal Robots Polyscope 5 are affected: Polyscope 5 <5.25.1 CVSS Vendor Equipment Vulnerabilities v3 9.8 Universal Robots Universal Robots Polyscope 5 Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') Background Critical Infrastructure Sectors: Critical Manufacturing Coun
View CSAF Summary Ruggedcom Rox contains an input validation vulnerability in the feature key installation process that could allow an authenticated remote attacker to execute arbitrary commands with root privileges on the underlying operating system. Siemens has released new versions for the affected products and recommends to update to the latest versions. The following versions of Siemens Ruggedcom Rox are affected: RUGGEDCOM ROX MX5000 vers:intdot/<2.17.1 RUGGEDCOM ROX MX5000RE vers:intd
View CSAF Summary Siemens Teamcenter is affected by multiple vulnerabilities which could potentially lead to a compromise in availability, integrity and confidentiality. Siemens has released new versions for the affected products and recommends to update to the latest versions. The following versions of Siemens Teamcenter are affected: Teamcenter V2312 vers:intdot/<2312.0014, vers:intdot/<2312.0009 (CVE-2026-33862, CVE-2026-33893, CVE-2024-4367) Teamcenter V2406 vers:intdot/<2406.0012,
View CSAF Summary Solid Edge SE2026 before Update 5 is affected by two file parsing vulnerabilities that could be triggered when the application reads specially crafted files in PAR format. This could allow an attacker to crash the application or execute arbitrary code. Siemens has released a new version for Solid Edge SE2026 and recommends to update to the latest version. The following versions of Siemens Solid Edge are affected: Solid Edge vers:intdot/<226.0.5 CVSS Vendor Equipm
View CSAF Summary The web server in SENTRON 7KT PAC1261 Data Manager Before V2.1.0 contains a request smuggling vulnerability in the Go Project's net/http package that could allow an attacker to retrieve authorization tokens that can be used to gain administrative control over the device. Siemens has released a new version for SENTRON 7KT PAC1261 Data Manager and recommends to update to the latest version. The following versions of Siemens SENTRON 7KT PAC1261 Data Manager are affected: SENTRON
View CSAF Summary Opcenter RDnL is affected by missing authentication in critical function in ‘ActiveMQ Artemis’. An unauthenticated attacker within the adjacent network could use the Core protocol to force a target broker to establish an outbound Core federation connection to an attacker-controlled rogue broker. This could potentially result in availability impacts or message injection into any queue via the rogue broker. Breaking the integrity of a message has a low impact due to missing auto
View CSAF Summary Ruggedcom Rox contains an improper access control vulnerability that could allow an authenticated remote attacker to read arbitrary files with root privileges from the underlying operating system's filesystem. Siemens has released new versions for the affected products and recommends to update to the latest versions. The following versions of Siemens Ruggedcom Rox are affected: RUGGEDCOM ROX MX5000 vers:intdot/<2.17.1 RUGGEDCOM ROX MX5000RE vers:intdot/<2.17.1 RUGG
View CSAF Summary SIMATIC S7 PLCs contain multiple vulnerabilities in the web server that could allow an attacker to perform cross-site scripting attacks. Siemens has released new versions for several affected products and recommends to update to the latest versions. Siemens is preparing further fix versions and recommends specific countermeasures for products where fixes are not, or not yet available. The following versions of Siemens SIMATIC S7 PLC Web Server are affected: SIMATIC Drive Contr
View CSAF Summary Multiple industrial devices contain a vulnerability that could allow an attacker to cause a denial of service condition. Siemens has released new versions for several affected products and recommends to update to the latest versions. Siemens is preparing further fix versions and recommends specific countermeasures for products where fixes are not, or not yet available. The following versions of Siemens Industrial Devices are affected: IE/PB LINK HA (6GK1411-5BB00) vers:all/* (
View CSAF Summary SIMATIC HMI Unified Comfort Panels before V21.0 are affected by a vulnerability that allows an unauthenticated attacker to access the web browser via the help link. This vulnerability allows an attacker to access the web browser through the Control Panel if it is not protected by the corresponding security mechanisms. This opens the possibility for the attacker to find backdoors, which might lead to unwanted misconfigurations. Siemens has released new versions for the affected
View CSAF Summary The SIPROTEC 5 devices do not use sufficiently random numbers to generate session identifiers. This could facilitate a brute-force attack against a valid session identifier which could allow an unauthenticated remote attacker to hijack a valid user session. The affected session identifiers are only used in a subset of the endpoints that are provided by the affected products. Siemens is preparing fix versions and recommends countermeasures for products where fixes are not, or no